ABB ACH580-01-12A7-4 HVAC AC Drive 5.5 kW 12.6 A


  • Part Number: ACH580-01-12A7-4
  • Category: Automation & Control
  • Manufacturer: ABB
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-105054
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Automation & Control > AC Drives

ACH580-01-12A7-4: 12.6 A of fan and pump control for buildings
Rated 5.5 kW with 12.6 A of nominal output current, the
ACH580-01-12A7-4
belongs to ABB’s ACH580-01 range, the wall-mounted HVAC line with BACnet MS/TP, Modbus RTU and N2 built in. It occupies frame R1. At 5.5 kW it is the largest R1 rating, so a lot of motor power fits the narrowest frame. ABB positions the family for fans, pumps and also for basic constant-torque duties such as compressors.
ABB equips the ACH580 with building functions rather than generic machine macros, among them motor preheating, an energy optimiser with kWh counters, stall and overload protection and Drivetune smartphone commissioning with the Bluetooth panel. See more ratings under
AC drives
; the sister platform is described on the
ABB ACS580 page
.
Technical specifications
Parameter
Specification
Type designation
ACH580-01-12A7-4
Platform
ACH580-01 wall-mounted HVAC drive
Input supply
Code 4: 380-415 V or 440-480 V, three-phase
Housing frame
R1
No-overload rating (400 V)
5.5 kW, 12.6 A
Light duty (400 V)
12 A, 5.5 kW
Light duty (480 V)
12 A, 7 hp
Enclosure options
IP21 standard; +B056 gives IP55
Size in IP21
373 mm with gland box (331 mm without) x 125 x 223 mm
IP21 net weight
4.6 kg
Size and weight in IP55
403 x 128 x 233 mm, 4.8 kg
Next sizes in table
Below: ACH580-01-09A5-4 (4 kW); above: ACH580-01-018A-4 (7.5 kW)
Duty ratings of the ACH580-01-12A7-4
The catalogue gives three ratings for this type. Nominal use is 12.6 A for 5.5 kW. Light-duty use on 380 to 415 V is 12 A for 5.5 kW, which allows 110% overload for one minute in ten (about 13.2 A, derived). On a 440 to 480 V supply the light-duty current is 12 A, matching 7 hp. ABB states that all ACH580 ratings apply at +40 degrees C ambient.
Frame R1 in IP21 form stands 373 mm tall including the gland box (331 mm without it), 125 mm wide and 223 mm deep, and weighs 4.6 kg. The IP55 build measures 403 x 128 x 233 mm at 4.8 kg. With a main switch or C1 filter variant the IP55 bo

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

ACH580-01-03A4-4
Request Inquiry
More Info
S803S-D25
Request Inquiry
More Info
S203-C80
Request Inquiry
More Info
AF52-30-00-13
Request Inquiry
More Info
S201M-C16
Request Inquiry
More Info
S203-C20
Request Inquiry
More Info
↑