ABB FDIO-01 Digital I/O Extension Module for ABB Drives


  • Part Number: FDIO-01
  • Category: Automation & Control
  • Manufacturer: ABB
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-105128
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Automation & Control > Automation Accessories

Extra digital I/O for ABB drives
The
FDIO-01
adds three digital inputs and two relay outputs to an ABB drive. It is the practical answer when a control cabinet needs mains-level inputs or heavier relay switching than the drive board offers.
Inputs take 24 to 250 V DC or 110 to 230 V AC, so they can read signals from contactors, auxiliary contacts or a mains-level alarm loop directly. Insulation above 4 kV isolates them from the drive.
Technical specifications
Parameter
Specification
Type designation
FDIO-01
Digital inputs
3, 24-250 V DC or 110-230 V AC
Relay outputs
2
Relay rating
5 A at 24 V DC, 1250 VA at 250 V AC
Contact material
AgNi
Isolation
Inputs isolated, insulation above 4 kV
Approvals
cULus
Mounting
Option slot or FEA-03
Inputs and relays
Two relay outputs carry 5 A at 24 V DC or 1250 VA at 250 V AC with AgNi contacts, enough for small contactors, signal lamps or alarm relays.
The module is cULus listed.
Application notes
It fits an option slot or an FEA-03 adapter when slots are limited.
Remember that AgNi contacts are not suited to very low-level signal switching.
Selection and planning notes
Digital I/O at mains voltage can save interposing relays. An AC input fed straight from a contactor auxiliary contact tells the drive that the bypass is closed; a relay output can drive a small contactor coil or a lamp. Remember to size an external fuse or miniature breaker for the relay circuit, and to respect the stated 5 A limit at 24 V DC, because DC loads are harder on contacts than AC loads.
Other options and drives are listed in
AC drives
; the
ABB ACS580 page
introduces the common platform. Tell us the load types so we can check the relay ratings with you.
Before power-up, read the terminal designations on the module label and compare them with the cabinet drawing. Mains-level inputs on an extension module are safe only when the wiring respects the insulation rules in the manual, so keep extra-low-voltage and mains circuits in separate cable ducts. After in

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

ACH580-01-03A4-4
Request Inquiry
More Info
S803S-D25
Request Inquiry
More Info
S203-C80
Request Inquiry
More Info
AF52-30-00-13
Request Inquiry
More Info
S201M-C16
Request Inquiry
More Info
S203-C20
Request Inquiry
More Info
↑