Taxonomy Path: Electrical & Power > Circuit Breakers
The
S201-C6
is a single-pole miniature circuit breaker in ABB’s System pro M compact S200 range, listed under order code 2CDS251001R0064. Overloads are handled thermally and short circuits magnetically, while the C characteristic lets ordinary inrush currents pass without nuisance tripping. ABB gives 6 kA short-circuit capacity to IEC/EN 60898-1, which covers common board duties such as a single 230 V lighting, control or socket circuit.
Related devices can be found under
circuit breakers
; for loads beyond 63 A look at the
SACE Tmax XT
series.
Technical specifications
Parameter
Specification
Model and order number
S201-C6 / 2CDS251001R0064
Pole count, curve and In
1P / C / 6 A
Ue under IEC/EN 60947-2
230 V AC
Magnetic trip window, 5-10 x In
30 to 60 A
Icn, rated short-circuit capacity
6 kA (IEC/EN 60898-1)
Terminal capacity
35 mm2 at top and bottom, 2.8 Nm
AC electrical life
20,000 operations
Degree of protection
IP20 (IP40 with enclosure cover)
Outline W x H x D
17.5 x 85 x 69 mm
Mechanical life
20,000 operations
Applicable standards
IEC/EN 60898-1 and IEC/EN 60947-2, plus UL 1077
Un under IEC/EN 60898-1
230/400 V AC (one pole)
Conventional currents, 1.13 and 1.45 x In
6.78 A over 1 h / 8.7 A within 1 h|no trip below 6.78 A for 1 h; trip within 1 h at 8.7 A|6.78 A held for an hour; 8.7 A trips inside an hour|6.78 A (no trip, 1 h) and 8.7 A (trip, 1 h)
Ics service capacity
7.5 kA
Icu under IEC/EN 60947-2
10 kA
Approx. weight, 125 g a pole
125 g
Selecting the 6 A C-curve
The C curve trips instantly between 5 and 10 times In, which for 6 A means 30 A to 60 A, and at 5 x In the delay is 0.1 to 15 s. The bimetal element holds at 6.78 A (1.13 x In) for one hour and must trip inside one hour at 8.7 A (1.45 x In); the reference temperature is 30 C. The permitted operating current falls to 5.7 A at 40 C, 5.3 A at 50 C and 4.9 A at 60 C according to the ABB table. Grouping matters too, with factors of 0.9, 0.8 and 0.75 for two or three, four or five and six or more adjacent
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |