Four 120 V AC inputs in a 12 mm POINT I/O module
The
Allen-Bradley 1734-IA4
reads four 120 V AC inputs in one non-isolated sinking group. It is only 12.1 mm wide, which lets mains-voltage contacts such as starter feedback, pressure switches and selector switches be brought into a POINT I/O station beside DC and analog modules.
The 2-point sibling is the 1734-IA2, and the conformal-coated version is 1734-IA4K. All three are covered by one installation instruction, series C.
Technical specifications
Parameter
Specification
Catalog number
1734-IA4 (1734-IA2 two-point; 1734-IA4K conformal coated), series C
Inputs
4, one group of 4, non-isolated, sinking
On-state voltage
65 V AC min, 120 V AC nominal, 132 V AC max
On-state current
4.0 mA at 65 V AC; 7.5 mA nominal at 120 V AC; 8.5 mA max at 132 V AC (60 Hz)
Off-state voltage / current
43 V AC max / 2.7 mA at 43 V AC
Input impedance, nominal
10.6 kOhm
Delay time
20 ms hardware filter plus programmable digital filter up to 65 ms in 1 ms steps
External AC supply
120 V AC nominal at 60 Hz; range 85 to 132 V AC, 47 to 63 Hz
POINTBus current
75 mA at 5 V DC
Power dissipation
0.50 W at 132 V AC (1.71 BTU/hr)
Isolation
240 V continuous; type tested 3250 V DC for 60 s, field side to system
Keyswitch position
8
Terminal base
1734-TB, TBS, TB3, TB3S, TOP, TOPS, TOP3 or TOP3S
Dimensions / weight
56.6 x 12.1 x 77.5 mm / 30.9 g
Operating temperature
-20 to +55 C
Temperature code
T4A (North American); T4 (IECEx, UKEX/ATEX)
Using AC inputs on a POINT I/O station
The module needs the 120 V AC supply brought to the terminal base as the sensing voltage, so the AC field wiring should be separated from the DC wiring with the right base. The long hardware delay of 20 ms plus the digital filter means AC inputs are suited to slow signals only. If the field device leaks current, the maximum off-state current of 2.7 mA at 43 V AC is the figure to compare against.
Ordering notes
The wiring base is ordered separately, and the keyswitch position of
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |