Taxonomy Path: Sensors & Transmitters > Temperature Instrumentation > Thermostats & Temperature Switches
KP 61 thermostat for evaporator and cold-room control from -30 to 15 C
Danfoss
060L110166
is a KP 61 thermostat with a 5 m capillary tube. The sensor is a 2.5 x 500 mm coiled capillary that is simply placed in the air stream or fixed to the evaporator, and the vapour charge keeps the reaction fast. Setting range covers -30 to 15 C, which includes deep-freeze defrost termination, cold room and chilled-air control, so the code is one of the most universal thermostats in refrigeration plant.
The data sheet describes the KP thermostats as single-pole double-throw temperature-operated switches that can be connected directly to a single-phase AC motor of up to roughly 2 kW or used in the control circuit of DC motors and large AC motors. They are used for regulation but also appear in safety monitoring systems.
Technical specifications
Parameter
Specification
Danfoss code number
060L110166
Type
KP61
Function
Thermostat with capillary tube sensor, automatic reset
Temperature range
-30 to 15 C
Differential (adjustable)
5.5-23 K at minimum setting; 1.5-7 K at maximum setting
Contact system
SPDT
Contact rating
AC15=10 A, 400 V; AC1=16 A, 400 V; AC3=16 A, 400 V; DC13=12 W, 220 V; LR=112 A, 400 V
Enclosure
IP30
Sensor
Capillary tube sensor 2.5 x 500 mm, vapour charge
Capillary tube length
5000 mm
Max. sensor temperature
120 C
Ambient temperature
-40 to 65 C
Cable entry
Rubber cable gland for 6-14 mm cable
Approvals as listed
BV; CCC; CE; CMIM; DNV; EAC; GL; LR; LVD; RINA; RoHS China; c UL us UL873, CS C22.2; UA
Net weight
0.47 kg
EAN
5702428516884
Setting the differential and placing the sensor
The differential changes with the setting on the scale: it is largest (5.5 to 23 K) at the bottom of the range and smallest (1.5 to 7 K) at the top. For a cold room kept at 2 C, set the scale near the upper range and use the differential spindle to avoid frequent compressor starts. When the thermostat is used to end defrost, place the sensor at the point on the coil that clears last.
The
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |