Hager NCN106A 1P 6 A C-Curve 10 kA MCB


  • Part Number: NCN106A
  • Category: Electrical & Power
  • Manufacturer: Hager
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:33
  • SKU: IS-110645
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Circuit Breakers

NCN106A: Hager MCB 1P 10kA/15kA C-6A 1M explained
The
Hager NCN106A
is a 1-pole thermal-magnetic miniature circuit breaker, rated 6 A with a C characteristic and a breaking capacity of 10 kA / 15 kA for a 1-module width. It protects a final or sub-distribution circuit against overload and short-circuit and also acts as the local isolating device. our engineering team supplies NCN106A in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
The catalogue description reads “MCB 1P 10kA/15kA C-6A 1M”, and each element of it has a practical meaning when you choose the breaker for a board. The table below turns the description into plain engineering terms so you can compare NCN106A with other references on a bill of quantities.
Element
Value
What it means in practice
MCB
Miniature circuit breaker
Thermal-magnetic device for DIN rail mounting in a distribution board
1P
1 protected pole
One pole that carries the release; the neutral is not switched
10 kA / 15 kA
Breaking capacity
Maximum fault level the device is rated to clear at the stated voltage
C-6A
C curve, 6 A
Trip characteristic and rated current at the 30 °C reference
1M
1 module
Width of 17.5 mm on the DIN rail
NCN106A technical specifications
Parameter
Specification
Manufacturer / part number
Hager / NCN106A
Description
MCB 1P 10kA/15kA C-6A 1M
Poles / curve
1P / C
Rated current In
6 A
Breaking capacity
10 kA at 230 V AC (IEC 60898-1), Icu 15 kA (IEC 60947-2), Ics 7.5 kA
Rated operational voltage Ue
230–400 V AC
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
6000 V
Frequency
50–60 Hz
Energy limitation class
3 (I²t)
Ingress protection
IP20
Operating temperature
−25 to 70 °C
Dissipation
1.33 W
Width x height x depth
17.5 x 83 x 70 mm
Conductors (screw terminals)
1–35 mm² rigid, 1–25 mm² flexible
Terminal torque
2.80 Nm
Standard pack
12 pieces per pack (catalogue)
Electrical endurance
4000 cycles
How the NCN106A protects the circuit
Inside NCN106A, a bimetal

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

CCC217J
Request Inquiry
More Info
SBN325
Request Inquiry
More Info
CD440B
Request Inquiry
More Info
SBN363
Request Inquiry
More Info
CD441J
Request Inquiry
More Info
SBN390
Request Inquiry
More Info
↑