Honeywell SPXCDALMRX Sensepoint XCD IR Methane Detector


  • Part Number: SPXCDALMRX
  • Category: Fire & Gas Systems
  • Manufacturer: Honeywell
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:33
  • SKU: IS-113156
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Fire & Gas Systems > Fire & Gas Detectors

A catalytic detector reads flammable gas by burning it on a bead. Honeywell SPXCDALMRX does the job with light instead. It is the Sensepoint XCD point detector fitted with a plug-in infrared sensor linearised to methane, mounted in an LM25 aluminium ATEX and IECEx housing with M20 entries. Choosing infrared rather than catalytic removes poisoning concerns and allows operation in atmospheres with little or no oxygen, which is why this part is requested for inerted vessels, biogas and landfill plant, and gas metering stations.
SPXCDALMRX in numbers
Parameter
Value
Sensor
Plug-in infrared hydrocarbon sensor, linearised to methane
Range
0 to 100 percent LEL default; selectable full scale 20 to 100 percent LEL in 10 percent steps
Calibration
Default 50 percent LEL; calibration gas 30 to 70 percent of the selected full scale
Response T90
Less than 30 s
Accuracy
Better than +/-1.5 percent LEL
Temperature
-20 to +55 degrees C
Alarms
20 percent LEL and 40 percent LEL, rising
Power
Up to 3.7 W
Output
4 to 20 mA sink or source; 3 relays; Modbus RTU optional
Housing
LM25 aluminium, 2.0 kg, IP66
Spare cartridge
SPXCDXSRXSS
Why SPXCDALMRX differs from SPXCDALMPX and SPXCDALMFX
The SPXCDALMRX is linearised to methane, while the SPXCDALMPX is linearised to propane and carries linear cross-sensitivity factors for ethylene, butane and pentane. The catalytic SPXCDALMFX instead addresses gas types 1 to 8. The infrared units have a response time of under 30 seconds, a narrower operating limit than catalytic units, and they cannot take advantage of the extended low-temperature range because the datasheet excludes the infrared and hydrogen sensors from it.
Best-fit applications
Natural gas receiving and metering stations where methane is the hazard.
Biogas digesters and landfill gas compressors in waste treatment plants.
Gas turbine enclosures and generator buildings fuelled with natural gas.
Inert-blanketed tanks and vessels, where catalytic beads need oxygen.
Plants in which silicone or

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

UDC1700
Request Inquiry
More Info
STG830
Request Inquiry
More Info
STA77S
Request Inquiry
More Info
STR735D
Request Inquiry
More Info
SPXCDASMRFD
Request Inquiry
More Info
TR23-H/U
Request Inquiry
More Info
↑