Honeywell XCD SPXCDALMG1 Hydrogen Detector 0-1000ppm


  • Part Number: XCD
  • Category: Fire & Gas Systems
  • Manufacturer: Honeywell
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:17
  • SKU: IS-100515
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Fire & Gas Systems > Fire & Gas Detectors

Overview
The Honeywell XCD hydrogen detector SPXCDALMG1 is a fixed gas detector configured for hydrogen (H2) measurement with a full scale range of 0-1000 ppm, housed in an LM25 aluminium enclosure with M20 cable entries. It is part of the Sensepoint XCD range of loop-powered, ATEX and IECEx approved gas detectors with a local display, configurable alarms and a 4-20 mA output.
Hydrogen detection matters wherever batteries are charged, where hydrogen is used as a process gas or where hydrogen sulfide cracking is a concern. The Honeywell XCD hydrogen detector measures hydrogen at low ppm levels, giving operators early warning before flammable concentrations build up.
Engineering & Design
The Sensepoint XCD transmitter platform accepts plug-in sensors: Surecell electrochemical sensors, poison-resistant catalytic flammable sensors and infrared sensors. For hydrogen, the detector measures 0-1000 ppm with a user-selectable full scale range and default alarm points, and reports via a 4-20 mA output that can be configured as sink or source.
Alarm set points, ranges, relay behaviour and the output mode are configured through the magnetic switch interface without opening the enclosure, which keeps the certification of the detector intact during commissioning and maintenance. The detector supports the complete Sensepoint XCD range of gases, so a site standardizing on the XCD platform can stock one transmitter type and the specific plug-in sensors for each hazard. For hydrogen service, the electrochemical cell is the drop-in sensing element that gives the ppm measurement this configuration is ordered with.
Two programmable alarm relays and one programmable fault relay provide local switching, and an optional MODBUS output enables remote diagnostics and configuration. The tri-colour backlit LCD shows gas readings and icons clearly, and all configuration is done with non-intrusive magnetic switches. The housing is LM25 aluminium with 2 x M20 cable/conduit entries, rated IP66, cer

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard