Taxonomy Path: Automation & Control > Isolator & Barrier
HART-capable Ex-i repeater power supply for 2-wire transmitters
The
JUMO Ex-i power supply/input isolating amplifier
(type 707530) operates intrinsically safe transmitters and mA current sources installed in a hazardous area. It supplies the connected 2-wire transmitter and passes the 0/4 to 20 mA measured value to the safe area. Wiring decides the mode: as a supply isolating amplifier for 2-wire transmitters, or as an input isolating amplifier for 4-wire transmitters and current sources.
The output can be active or passive, and HART communication signals pass in both directions on the Ex and non-Ex side. A switch on the front adds a resistor in the output circuit to raise the HART impedance in low-resistance systems. A single narrow housing, 17.5 mm wide, with 3-way isolation and a 24 to 230 V AC/DC wide-range supply keeps cabinet planning simple.
In repeater power supply operation it provides about 16 V at 20 mA to the transmitter, and the output can be a current of 0 to 20 or 4 to 20 mA, or a voltage of 0 to 5 or 1 to 5 V. The green LED shows that the supply voltage is present.
Technical specifications
Parameter
Specification
Type
707530; 1 channel; order code 707530/38
Input
0 to 20 mA or 4 to 20 mA; transmitter supply above 16 V at 20 mA, above 15.3 V at 22.5 mA
Output
Current 0/4 to 20 mA active or passive (external source 14 to 26 V); voltage 0 to 5 V or 1 to 5 V (250 Ohm internal)
Burden
Below 600 Ohm at 20 mA; below 525 Ohm at 22.5 mA
Accuracy
Transmission error max. 0.1 % of end value, typical 0.05 %; temperature coefficient below 0.01 %/K
Step response
Below 600 us (10 to 90 %, 4 to 20 mA step)
Supply
AC/DC 24 to 230 V, -20 to +10 %, 50 to 60 Hz; below 80 mA at 24 V DC; below 1.6 W
Isolation
Input/output and input/supply 375 V peak per EN 60079-11; test voltage 2.5 kV AC; rated insulation 300 V rms
Safety data (supply mode)
Uo 25.2 V; Io 93 mA; Po 587 mW; gas group IIC: Lo 2 mH, Co 107 nF
Safety data (input mode)
Ui 30 V; Ii 150 mA; Li and Ci negligible
A
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |