Lovato GA063A Three-Pole Switch Disconnector 63 A


  • Part Number: Lovato
  • Category: Electrical & Power
  • Manufacturer: Lovato Electric
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-108761
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Switchgear, Enclosures & Distribution

Lovato GA063A three-pole switch disconnector, 63 A
The
Lovato GA063A
is a three-pole load-break switch disconnector rated 63 A for use as a main or local isolator. It carries 63 A in AC-21A, AC-22A and AC-23A at 400 and 500 V, has a rated insulation voltage of 1000 V, and mounts on a 35 mm DIN rail or by screws. our engineering team supplies the GA063A in Oman and the GCC as an independent supplier in Muscat.
In the code, GA is the switch disconnector family and 063 is the rated thermal current of 63 A, Other ratings in the same group include GA016A, GA025A, GA032A, GA080A and GA125A.
GA063A technical specifications
Parameter
Specification
Manufacturer / part number
Lovato / GA063A
Poles
3
Thermal current Ith
63 A
Insulation Ui / Uimp
1000 V / 8 kV
AC-21A / AC-22A / AC-23A at 400 and 500 V
63 A
AC-22A / AC-23A at 690 V
47 A
Motor power AC-23A
30 kW at 400 V; 45 kW at 690 V
Short time current Icw (1 s)
2.5 kA
Conditional short-circuit current
50 kA with gG 63 fuses
Making / breaking AC-23A 400 V
630 A / 504 A
Life
30,000 mechanical; 30,000 electrical
Terminals
Pillar M8; 4 to 70 mm²; 5 to 6 Nm
Dissipation per pole
1.6 W
UL rating
UL98; 60 A general use; 600 V maximum
UL motor ratings
20 HP at 240 V; 40 HP at 480 V and 600 V
Temperature
-25 to +55 °C
Altitude
3000 m
Weight
388 g
What a switch disconnector does, and does not do
A switch disconnector is a manually operated device that can switch load current and then provide a visible isolating gap for safe work. It is not a protective device: it does not trip on overload or short circuit, and it relies on fuses or an upstream breaker for that. The data sheet therefore quotes a conditional short-circuit current of 50 kA when protected by gG 63 fuses and a short-time withstand of 2.5 kA for one second.
The AC-23A category is the one that matters for motors: it permits switching of motors under load, including occasional stopping of a running motor, up to 30 kW at 400 V. At 690 V the current drops to 47 A.
Where the GA063A fit

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

Lovato
Request Inquiry
More Info
Lovato
Request Inquiry
More Info
Lovato
Request Inquiry
More Info
Lovato
Request Inquiry
More Info
Lovato
Request Inquiry
More Info
Lovato
Request Inquiry
More Info
↑