Taxonomy Path: Automation & Control > Industrial Communications
How the TCC-100 extends a link
TCC-100
is listed by Moxa as: RS-232 to RS-422/485 converter. A compact industrial converter that bridges RS-232 devices to RS-422 or RS-485 networks, extending cable reach and adding electrical isolation in the TCC-100I variant.
From the manufacturer’s specification table, the power input is 12 to 48 VDC; operating temperature is -20 to 60°C (-4 to 140°F); dimensions are 67 x 100.4 x 22 mm (2.64 x 3.93 x 0.87 in); weight is 148 g (0.33 lb); the enclosure is rated IP30.
Standards and approvals printed for this model include safety standard UL 60950-1. Approvals can differ between variants of a series, so check the one on the exact order code.
Technical specifications
Parameter
Specification
No. of Ports
2
Connector
Terminal block
Serial Standards
RS-232; RS-422; RS-485
Baudrate
50 bps to 921.6 kbps (supports non-standard baudrates)
Pull High/Low Resistor for RS-485
1 kilo-ohm, 150 kilo-ohms
RS-485 Data Direction Control
ADDC (automatic data direction control)
Terminator for RS-485
N/A, 120 ohms, 120 kilo-ohms
RS-232
TxD, RxD, RTS, CTS, GND
RS-422
Tx+, Tx-, Rx+, Rx-, RTS (optional), CTS (optional), GND
RS-485-2w
Data+, Data-, GND
RS-485-4w
Tx+, Tx-, Rx+, Rx-, GND
Input Current
47 mA (max)
Input Voltage
12 to 48 VDC
No. of Power Inputs
1
Overload Current Protection
Supported
Power Connector
Terminal block (for DC models)
Housing
Metal
IP Rating
IP30
Dimensions
67 x 100.4 x 22 mm (2.64 x 3.93 x 0.87 in)
Weight
148 g (0.33 lb)
Installation
Wall mounting; DIN-rail mounting (with optional kit)
Operating Temperature
-20 to 60°C (-4 to 140°F)
Storage Temperature (package included)
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)
EMC
EN 55032/35
EMI
CISPR 32, FCC Part 15B Class A
EMS
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV; IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m; IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV; IEC 61000-4-5 Surge: Power: 1 …
Safety
UL 60950-1
Vibration
IEC 60068-2-6
Environmental Testing
IEC
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |