Taxonomy Path: Automation & Control > Isolator & Barrier
MTL4541A: isolating a self-powered transmitter on a backplane
Plenty of field instruments, particularly analyser outputs and 4-wire transmitters, bring their own power and simply deliver a 4-20 mA signal. The MTL MTL4541A is the module that connects such a source from a hazardous area to a safe-area control system through galvanic isolation. It belongs to the MTL4500 backplane range, whose modules plug into a multiway connector that supplies power and safe-area signals, while the field wiring plugs into the front of the module.
Specification highlights of the MTL4541A
Model
MTL4541A (MTL4541AS is the sink version)
Mounting
MTL4500 backplane, 16.0 mm pitch
Channels
one
Input range
4 to 20 mA; 1.0 to 21.5 mA under/over-range
Input impedance for HART
above 230 ohm at terminals 1 and 2
Maximum input voltage drop
below 6.6 V (330 ohm load at 20 mA)
Output range
4 to 20 mA; 1.0 to 21.5 mA under/over-range
Load, conventional transmitters
0 to 360 ohm
Load, smart transmitters
250 ohm plus or minus 10 percent
Output ripple
below 50 microamps peak to peak up to 80 kHz
Transfer accuracy
better than 20 microamps at 20 degrees C
Temperature drift
below 1 microamp per degree C
Settling
within 200 microamps of final value after 20 ms
Supply current
50 mA at 20 V; 45 mA at 24 V; 35 mA at 35 V
Dissipation
0.8 W at 24 V
Safety
Um 253 V rms or dc; 8.6 V diode at terminals 1-2
Reading the MTL4541A line-fault behaviour
Because the module repeats the field current, a broken cable or shorted loop appears at the control system as an open or short circuit current, which the control system can alarm on. The datasheet makes this a stated benefit of the analogue input units such as the MTL4541 and MTL5541 types. The diode drop of 8.6 V at terminals 1 and 2 should be added to the loop voltage and considered when working out the permitted load capacitance.
When the transmitter is non-energy-storing apparatus no larger than 1.5 V, 0.1 A and 25 mW, it can be connected to any intrinsically safe loo
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |