MTL MTL5582B RTD Resistance Isolator


  • Part Number: MTL
  • Category: Automation & Control
  • Manufacturer: MTL (Eaton)
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:33
  • SKU: IS-112669
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Automation & Control > Isolator & Barrier

MTL5582B repeats resistance rather than converting it
Not every control system wants a 4-20 mA signal from a temperature sensor. Some wish to wire an RTD directly to an input card that measures resistance. The MTL MTL5582B solves this: it connects to a 2-, 3- or 4-wire RTD in a hazardous area, isolates it, and presents the same resistance to the safe-area equipment. The manufacturer positions it as a non-configurable alternative to the MTLx575 for applications where a resistance input is preferred.
MTL5582B specification
Model
MTL5582B
Function
resistance isolator, repeats RTD signals
Channels
one
Sensor
2-, 3- or 4-wire RTD, 100 ohm at 0 degrees C (BS 1904 / DIN 43760)
Resistance range
10 to 400 ohm
Excitation current
200 microamps nominal
Output range
10 to 400 ohm from a 100 microamp to 5 mA source
Open-circuit action
upscale, nominal 420 ohm
Transfer accuracy
better than 0.15 ohm at 1 to 5 mA; better than 0.25 ohm at 0.5 to 1 mA
Drift
10 milliohm per degree C typical
Response
within 4 percent of final value in 1 s
Current draw
33 mA at 24 V; 35 mA at 20 V; 28 mA at 35 V
Dissipation
0.8 W at 24 V; 1.0 W at 35 V
Safety (terminals 1 and 3)
Uo 1.2 V, Io 4 mA, Po 1.2 mW
Safety (terminals 1, 3, 4, 5)
Uo 6.51 V, Io 10 mA, Po 17 mW
LED
green, power
Wire count flexibility: a feature of the MTL5582B
The datasheet stresses that the number of wires on the safe-area side does not have to match the hazardous-area side. A 3-wire RTD can be repeated as a 4-wire output if the receiving system needs it, or the other way around. The switches select the mode and the module ships set for 3-wire, which suits the Pt100 three-wire sensors that make up most installations.
This is handy during a control-system upgrade where the sensors stay but the input cards change.
Comparison with MTL5576-RTD and MTL5573
MTL5576-RTD and MTL5573 both produce 4-20 mA and are configured from a PC. The MTL5582B needs no software, has a single green power LED and no configuration, and is simple enough that

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

MTL
Request Inquiry
More Info
MTL
Request Inquiry
More Info
MTL
Request Inquiry
More Info
MTL
Request Inquiry
More Info
MTL
Request Inquiry
More Info
MTL
Request Inquiry
More Info
↑