Oldham OLCT 80 Gas Detector Transmitter


  • Part Number: OLCT
  • Category: Fire & Gas Systems
  • Manufacturer: Oldham
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:17
  • SKU: IS-102154
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Fire & Gas Systems > Fire & Gas Detectors

Overview
The
Oldham OLCT 80
is a fixed detector-transmitter from Teledyne Oldham Simtronics for flammable gases, toxic gases and oxygen in hazardous industrial areas. It accepts pre-calibrated sensor blocks based on catalytic, electrochemical, infrared or semiconductor principles, displays the reading locally and can switch alarms itself through three integrated relays. Configuration and calibration are carried out non-intrusively with an intrinsically safe infrared remote control, and remote sensor versions in flameproof (XP) and intrinsically safe (IS) form allow the sensing head to be placed away from the transmitter.
our engineering team supplies the Oldham OLCT 80 to oil and gas operators, refineries, chemical and fertiliser plants, water treatment facilities and power stations in Oman and the GCC. Our engineers in Muscat help customers select sensor types, ranges and wiring modes, and we provide engineering support for projects and maintenance in Muscat, Sohar, Duqm and Salalah.
Measurement Principle
The sensing technology of the Oldham OLCT 80 depends on the target gas. Flammable gases are detected with catalytic sensors over 0 to 100% LEL or with infrared sensors, while thermal conductivity (catharometer) cells measure methane or hydrogen up to 100% vol. Toxic gases and oxygen are measured with electrochemical cells, in which the gas reacts at an electrode and produces a current proportional to its concentration. The brochure lists electrochemical cells for O2, CO, H2S, NO, NO2, Cl2, H2, HCl, HCN, NH3, O3, PH3, ClO2, SiH4 and AsH3, and a semiconductor sensor for volatile organic compounds.
The Oldham OLCT 80 applies smart signal processing to the 4-20 mA loop. Values between 0 and 3.2 mA and above 20 mA are used to signal line faults, sensor faults, electronics faults, calibration inhibition and maintenance calls for drift, so the controller can tell a gas alarm from an equipment problem. Internal self-diagnostics and digital logic keep analog and digital values c

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.