Taxonomy Path: Automation & Control > Automation Accessories
H3CR-AP: 11-pin multi-mode timer for voltage-type control signals
The Omron
H3CR-AP
is the voltage-input version of the 11-pin H3CR-A multifunctional timer. Its start, reset and gate terminals respond to an applied voltage rather than to a contact closure, which suits signals coming from PNP sensors, PLC outputs or other powered sources. our engineering team supplies the H3CR-AP in Oman and the GCC as an independent supplier in Muscat. Read on for the decoded part number and the selection points that matter.
H3CR-A
is the multifunctional timer type with eight selectable operating modes.
No pin number after A means the 11-pin form.
P
means voltage input (PNP type); without P the input is no-voltage (NPN).
No further letter means a DPDT relay output.
Supply voltage is added when ordering: 100-240AC/100-125DC or 24-48AC/12-48DC.
The voltage input removes the need for an interposing relay when a PLC output or 24 V sensor is the trigger, which is why the H3CR-AP is often specified in control panels that are already built around solid-state signals.
H3CR-AP technical specifications
Parameter
Specification
Manufacturer / part number
Omron H3CR-AP
Pin type / mounting
11-pin plug-in
Time range
0.05 s to 300 h
Operating modes
A, B, B2, C, D, E, G and J
Input type
Voltage input (PNP)
Input levels, 100-240 V version
High 85 to 264 VAC / 85 to 137.5 VDC; low 0 to 10 VAC/VDC
Input levels, 24-48 V version
High 20.4 to 52.8 VAC / 10.8 to 52.8 VDC; low 0 to 2.4 VAC / 0 to 1.2 VDC
Max. capacitance between input lines
1,200 pF (terminals 6 and 7)
Output
DPDT relay
Power consumption, 100-240 V version
Relay ON approx. 2.5 VA (2.2 W); relay OFF approx. 1.8 VA (1.7 W) at 240 VAC, 60 Hz
Power consumption, 24-48 V version
Relay ON approx. 0.9 W; relay OFF approx. 0.3 W at 24 VDC
Rated supply voltage
100 to 240 VAC (50/60 Hz) / 100 to 125 VDC, or 24 to 48 VAC (50/60 Hz) / 12 to 48 VDC
Operating voltage range
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Contact rating
5 A at 250 VAC
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |