Taxonomy Path: Automation & Control > Isolator & Barrier
What the Pepperl+Fuchs KFA6-DWB-Ex1.D does
Installations without a 24 V DC bus sometimes still need hazardous-area speed supervision, and the Pepperl+Fuchs KFA6-DWB-Ex1.D answers that case. It is an isolated barrier powered directly from 230 V AC (plus or minus 10 percent, 18 mA, no more than 2 VA) that reads a NAMUR sensor or dry contact from a hazardous area and reports overspeed or underspeed through two relays.
Settings are made with the on-board keypad, and the result of every comparison is visible on the display. The monitor is one of the models that tolerate rotation measurements from 1 mHz up to 5 kHz.
Quick facts
Supply 230 V AC, terminals 23 and 24, rated current 18 mA
Input I intrinsically safe on terminals 1+ and 3-; Uo 10.1 V, Io 13.5 mA, Po 34 mW
Input II on terminals 13+ and 14- for the 1 to 1000 s start-up override
Outputs: two relays, 10-11-12 and 16-17-18
SIL 2 according to IEC/EN 61508 and IEC/EN 61511
KFA6-DWB-Ex1.D specification sheet
Parameter
Value
Supply
230 V AC plus or minus 10 percent, 18 mA, up to 2 VA
Maximum safe voltage Um
253 V AC
Input frequency
0.001 to 5000 Hz, pulses longer than 50 microseconds
Measuring accuracy
0.1 percent of the measured value
Active / passive level of input II
above 4 mA for at least 100 ms / below 1 mA
Open-circuit voltage / short-circuit current of input II
18 V / 5 mA
Line-fault thresholds
breakage 0.15 mA or less; short circuit above 6.5 mA
Relay rating
253 V AC / 2 A / cos phi 0.7 or better; 40 V DC / 2 A
Response delay
200 ms or less
Insulation of start-up override to supply
reinforced, 300 Veff
Ex ia certificate
TUV 99 ATEX 1408; IECEx TUN 03.0000
Zone 2 certificate
TUV 02 ATEX 1885 X, Ex nA nC IIC T4 Gc
Dimensions
40 x 119 x 115 mm, housing type C2, 300 g
Ambient temperature
-20 to 60 degrees C
Why choose the 230 V AC build of the DWB family
Brownfield plants in the Gulf often keep a 230 V AC instrument supply for panel-mounted equipment, with no DC rails running through the field cabinets. Specifying
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |