Taxonomy Path: Automation & Control > Isolator & Barrier
KFD2-GUT-1.D temperature converter with two trip relays
The KFD2-GUT-1.D is a universal temperature signal conditioner. It takes the signal of a resistance thermometer, a thermocouple, a potentiometer or a voltage source, isolates it, and delivers a proportional 0/4 to 20 mA output plus two relay contacts that can be set as limit values. A display and keypad on the front allow local configuration, and the PACTware software is available for configuration from a PC.
our engineering team supplies the KFD2-GUT-1.D in Oman and the GCC as an independent supplier in Muscat. This page explains the input options, the safety-related features and the points to confirm for a temperature-monitoring loop.
What KFD2-GUT-1.D stands for
The KFD2-GUT-1.D is a type designation of the Pepperl+Fuchs K-System, named in the datasheet as a temperature converter with trip values. It is a 1-channel signal conditioner with 24 V DC supply through the Power Rail. The housing is the wider C2 type, 40 mm, because it contains two relays in addition to the analog output.
The datasheet lists the function as a conditioner with galvanic isolation between field and control circuits, and shows up to SIL 2 under IEC/EN 61508 and IEC/EN 61511. As with all safety ratings, the figures are valid only when the device is used within the conditions given in the manufacturer safety documentation.
Technical specifications of the KFD2-GUT-1.D
Parameter
Specification
Manufacturer / part number
Pepperl+Fuchs / KFD2-GUT-1.D
Function
Universal temperature converter with 2 trip relays, 1 channel
RTD inputs
Pt100, Pt500, Pt1000, Ni100, Ni1000; 2-, 3- or 4-wire; lead resistance max. 50 Ω
Thermocouples
Types B, E, J, K, L, N, R, S, T (IEC 584-1); internal and external cold junction compensation
Potentiometer
0.8 … 20 kΩ, 2-, 3- or 5-wire
Voltage
0 … 10 V, 2 … 10 V, 0 … 1 V, -100 … 100 mV
Analog output
0 … 20 mA or 4 … 20 mA, load max. 650 Ω
Fault signalling
Downscale ≤ 3.6 mA, upscale ≥ 21 mA (NAMUR NE43); LEDs per NAMUR NE44
R
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |