KFD2-STC5-2 two-channel SMART transmitter power supply
The KFD2-STC5-2 puts two complete SMART transmitter supply channels into a single 20 mm wide K-System housing. Each channel powers a 4-20 mA field transmitter, isolates it from the control system and hands on both the analog value and any superimposed HART communication. For a marshalling cabinet with many instruments, doubling the channel density per rail metre is the main reason to choose this module over the single-channel KFD2-STC5-1.
our engineering team supplies the KFD2-STC5-2 in Oman and the GCC as an independent supplier in Muscat. This page explains the channel layout, the limits that govern loop design and the points to settle before ordering.
What the KFD2-STC5-2 designation tells you
The KFD2-STC5-2 follows the naming of its sibling KFD2-STC5-1, and the datasheet header identifies it as a 2-channel signal conditioner with a 24 V DC supply through the Power Rail, input for 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, and output 4 to 20 mA in sink or source mode.
Note that the two channels share a housing and a supply but not their signal circuits: the datasheet lists output-to-output isolation as functional insulation with a rated voltage of 50 V AC, while each input stays separated from its outputs and from the supply.
Technical specifications of the KFD2-STC5-2
Parameter
Specification
Manufacturer / part number
Pepperl+Fuchs / KFD2-STC5-2
Function
SMART transmitter power supply, 2 channels, galvanic isolation
Supported SMART protocols
HART, BRAIN, Foxboro
Field connections
Channel I: terminals 1+, 2-, 3; channel II: terminals 4+, 5-, 6
Input signal
4 … 20 mA per channel
Available voltage to transmitter
≥ 16 V at 20 mA; ≥ 20 V at 4 mA
Open circuit voltage / short-circuit current
23 V / 25 mA
Output signal
4 … 20 mA per channel, sink or source mode
Output load
0 … 600 Ω; internal 250 Ω resistors at terminals 9 and 12
External loop supply (sink mode)
2 … 30 V DC
Supply
18 … 30 V DC
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |