Taxonomy Path: Automation & Control > Isolator & Barrier
KFD2-STC5-Ex1.H: higher voltage for demanding transmitters
Some SMART transmitters, especially older analyser heads, flow meters with heaters or devices with long cable runs, need more voltage than a standard supply provides. The Pepperl+Fuchs KFD2-STC5-Ex1.H raises the available field voltage to 17 V DC at 20 mA and 21 V at 4 mA (24 V open circuit), against 16 V and 20 V for the standard model.
In every other respect it is a one-channel barrier with a 4 to 20 mA output that can be configured as sink or source on the safe side.
Selected features
High field voltage 17 V DC at 20 mA
Output 4 to 20 mA into 0 to 800 ohm; overload above 25 mA
If the external supply is above 19 V, a load of at least (V minus 19) divided by 0.02 ohm is required, and the internal 250 ohm resistor at terminal 9 may serve as that load
HART, BRAIN and Foxboro supported
Extended ambient range up to 70 degrees C under the mounting conditions described in the manual
KFD2-STC5-Ex1.H figures
Parameter
Value
Supply
18 to 30 V DC, up to 1 W dissipation, up to 1.6 W consumption
Input
4 to 20 mA, terminals 1+, 2-, 3
Open-circuit voltage / short-circuit current
24 V / 25 mA
Available voltage
17 V at 20 mA, 21 V at 4 mA
Output
4 to 20 mA sink or source, 0 to 800 ohm
Settling time
500 microseconds
Safe-side values
Uo 27.2 V, Io 93 mA, Po 633 mW
Certificate
CML 17 ATEX 2029X
Ambient
-20 to 60 degrees C (up to 70 degrees C with mounting conditions)
Dimensions, mass
20 x 124 x 115 mm, about 200 g
Deciding whether you need the H version
Add up the minimum operating voltage of the transmitter and the voltage drop of the cable at 20 mA. A transmitter that needs 15.5 V and sits on a 100 ohm cable loop (2 V drop) would be at the edge with a supply that delivers 16 V, but gets 1.5 V of margin with 17 V. In practice the H variant is the safe pick when the transmitter datasheet quotes a minimum of 15 V or more, or when a hazardous-area junction box adds protective components in series.
KFD2-STC5-Ex1.H compared with
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |