Taxonomy Path: Automation & Control > Isolator & Barrier
KFD2-UT2-Ex2-1: voltage-output temperature barrier
Some PLC and DCS input cards read 1 to 5 V instead of 4 to 20 mA, and for those systems the Pepperl+Fuchs KFD2-UT2-Ex2-1 replaces the current-output UT2-Ex2. Its two intrinsically safe input channels accept thermocouples, RTDs, potentiometers and millivolt sources from the hazardous area, and each channel produces a voltage of 0 to 5 V or 1 to 5 V with an output resistance of 5 ohm or less and a load of at least 10 kilohm.
Everything else about the module is shared with the current version: PACTware configuration, signal-splitter operation, line-fault and sensor-burnout detection, and the 20 mm wide B2 housing.
What the voltage outputs mean in practice
Terminals 7- and 8+ carry output I; terminals 10- and 11+ carry output II
Fault signal downscale 0 V or 0.5 V, upscale 5.375 V
Accuracy of the 1 to 5 V output: 4 mV from 0 to 103.1 percent of span; of the 0 to 5 V output: 4 mV from 0.3 to 102.5 percent of span
Supply 20 to 30 V DC on terminals 14+ and 15- or from the Power Rail; power dissipation 0.8 W
Datasheet values for KFD2-UT2-Ex2-1
Parameter
Value
Channels
2 isolated, signal-splitter capable
Output signal
0 to 5 V or 1 to 5 V
Output resistance / load
5 ohm or less / 10 kilohm or more
Supply
20 to 30 V DC, 0.8 W maximum
Pt100 deviation after calibration
0.06 percent of reading in K plus 0.1 K (4-wire)
Thermocouple deviation
0.05 percent of reading plus 1 K (1.2 K for R and S), including 0.8 K CJC error
Millivolt deviation
50 microvolts
Potentiometer deviation
0.05 percent of full scale, excluding lead resistance
Supply influence
less than 0.01 percent of span
Safe-side entity values
Uo 9 V, Io 22 mA, Po 50 mW
ATEX
CESI 04 ATEX 143; TUV 02 ATEX 1797 X
Zone 2 marking
Ex nA II T4 for the non-intrinsically safe side
Insulation
safe electrical isolation, peak 375 V (IEC/EN 60079-11)
Mechanical
20 x 119 x 115 mm, about 130 g, screw terminals
Using one sensor for two receivers
In splitter mode a single thermocouple on c
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |