Taxonomy Path: Automation & Control > Isolator & Barrier
KFU8-CRG2-Ex1.D: universal-supply transmitter barrier with relays
A plant that has only 24 V DC in one cabinet and 230 V AC in the next would need two spare types for the same function. The Pepperl+Fuchs KFU8-CRG2-Ex1.D removes that headache with a universal supply of 20 to 90 V DC or 48 to 253 V AC. The module is an intrinsically safe transmitter supply: it energises a 2-wire or 3-wire transmitter in a hazardous area, isolates the signal and outputs a scaled current plus two alarm relays.
Its feature set is that of the CRG2 family, including a display in physical units, linearisation with up to 20 points, adjustable delays and PACTware configuration.
Main features
Supply on terminals 23 and 24; 2 W / 3 VA dissipation, 2.2 W / 4 VA consumption
Ex ia input on terminals 1, 2, 3 with Uo 25.8 V, Io 93 mA and Po 0.603 W
Output III: 0 to 20 mA or 4 to 20 mA, up to 650 ohm; relay I on 10, 11, 12 and relay II on 16, 17, 18
Fault signal downscale 3.6 mA or less, upscale 21.5 mA or more (NAMUR NE43)
Reinforced insulation between output III and supply, interface and supply
KFU8-CRG2-Ex1.D specification
Parameter
Value
Supply
20 to 90 V DC or 48 to 253 V AC
Input signal
0/4 to 20 mA; available voltage above 15 V at 20 mA
Open-circuit voltage / short-circuit current
24 V / 33 mA
Line fault limits
breakage below 0.2 mA; short circuit above 22 mA
Accuracy
input under 30 microamps; output under 20 microamps
Delay range
0 to 250 s
Relay contacts
250 V AC / 2 A / cos phi 0.7 or better; 40 V DC / 2 A
Reaction time
under 650 ms at a step of 0 to 20 mA (90 percent)
ATEX certificate
TUV 01 ATEX 1701, marking [Ex ia Ga] IIC
Second entity set
Uo 25.8 V, Io 112 mA, Po 720 mW
Dimensions, mass
40 x 119 x 115 mm, housing C2, 300 g
Ambient
-20 to 60 degrees C
Why a universal supply helps
Brownfield sites in the Gulf frequently mix control voltages: 24 V DC for new skids, 110 V DC for switchgear batteries, 230 V AC for lighting panels. A single module covering 20 to 90 V DC and 48 to 253 V AC re
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |