PULS YR40.242 12-28V 40A MOSFET Dual Redundancy Module


  • Part Number: YR40.242
  • Category: Electrical & Power
  • Manufacturer: PULS
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-106326
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Power Modules

A low-loss MOSFET module for 1+1 and N+1 24 V redundancy
The
PULS YR40.242
is a dual-input redundancy module that replaces the usual decoupling diodes with MOSFETs. According to the datasheet this reduces heat and voltage drop: 72 mV at 2 x 10 A, 140 mV at 2 x 20 A, and only 1.7 W loss at 20 A or 5.9 W at 40 A output. That is why the module is only 36 mm wide with a rugged metal housing. It is intended for N+1 and 1+1 redundant systems and is suitable for all DIMENSION power supplies except the QT20 and QTD20 series.
The datasheet also mentions the YR40.241, which has an additional circuit that generates a supply voltage for the internal MOSFETs even when the output is in short circuit, making it suitable for any power supply. The YR40.242 does not need an auxiliary voltage.
Technical specification
Parameter
Specification
Order number
YR40.242 (12-28 V standard unit)
Input voltage
DC 12-28 V plus/minus 30 %; voltage range 8.4 to 36.4 Vdc; input circuitry must meet SELV
Input current
2 x 0 to 20 A continuous; 2 x 20 to 32.5 A for 5 seconds
Output current
0 to 40 A continuous; 40 to 65 A for 5 seconds (160 % peak load); max. 26 A at voltages below 6 V in overload or short circuit
Voltage drop, input to output
typ. 72 mV at 2 x 10 A; 112 mV at 1 x 20 A; 140 mV at 2 x 20 A
Power losses
typ. 230 mW at no load; 1.7 W at 2 x 10 A; 2.4 W at 1 x 20 A; 5.9 W at 2 x 20 A
Reverse current / voltage
max. 1 mA per input at 24 V; max. 40 Vdc applied to the output continuously
Protection
Reverse input polarity protection; IP20; class of protection III (no PE required)
Terminals
Screw terminals; input 0.5-6 mm2 solid, 0.5-4 mm2 stranded (7 mm stripping); output 0.5-16 mm2 solid, 0.5-10 mm2 stranded (12 mm stripping); negative distribution terminal included
Operating climate
Ambient -40 C to +70 C with 1 A per degree of output derating above +60 C; humidity 5 to 95 %; full rating to 2000 m, then 2.5 A or 5 C per 1000 m
Mechanical stress
Vibration to 500 Hz at 2 g; shock 30 g for 6 ms

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

CP10.241
Request Inquiry
More Info
QS20.241
Request Inquiry
More Info
QT40.241
Request Inquiry
More Info
XT40.241
Request Inquiry
More Info
CS10.241
Request Inquiry
More Info
MLY10.241
Request Inquiry
More Info
↑