Taxonomy Path: Sensors & Transmitters > Temperature Instrumentation > Thermostats & Temperature Switches
The
TUC407F001
is the safety temperature limiter (STB) version of the Sauter TUC universal thermostat. It has an adjustable limit between 95 and 130 degrees C, a 0.7 m capillary tube with a 76 mm sensor cartridge and a 100 mm brass thermowell, and the contact switches to the safe side if the capillary tube breaks, which is the property that qualifies an STB for safety duty on hot-water and heat-transfer plant.
A fail-safe limiter for hot-water and heating plant
A temperature limiter (TB or STB) is not a controller: once the set temperature is exceeded it latches and stays off until the temperature has fallen by at least the minimum switching difference and someone presses RESET with a tool. The datasheet states that the STB has the same functions as the TB, but the contact also switches to the safe side if the capillary tube is damaged. Because it is classified as category IV under the Pressure Equipment Directive 2014/68/EU, the STB is described as suitable for safety applications.
Key features from the datasheet
Safety temperature limiter with fail-safe action on capillary break
Certified to EN 14597 (TÜV ID 0000046121 for TUC207F003, TUC407F001 and TUC407F002)
PED 2014/68/EU category IV for the safety types
Temperature compensation minimises the shift of the change-over point
Setpoint adjustable only with a tool; RESET required after a trip
100 mm thermowell supplied (max. 12 bar); two housings can be joined as a monitor-limiter double thermostat
Technical specification
Parameter
Specification
Type
TUC407F001
Function
STB, safety temperature limiter
Setting range
95 to 130 °C
Switching difference
≤ 20 K
Capillary tube length
0.7 m
Sensor cartridge length (±12 mm)
76 mm, Ø 6.5 mm
Thermowell
100 mm, brass
Maximum sensor temperature
160 °C
Switch
Single-pole change-over
Max. load
Terminals 1-2: 230 V~, 10(2.5) A on the normally closed contact; terminals 1-4: 230 V~, 2(0.4) A
Min. load
24 V =/~, 100 mA
Switching point accuracy (STW, TB, STB)
0 / -9 K at the adjustmen
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |