Schneider Electric A9F45216 Acti9 iC60N 2P 16A D MCB


  • Part Number: A9F45216
  • Category: Electrical & Power
  • Manufacturer: Schneider Electric
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-109607
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Circuit Breakers

A9F45216: Acti9 iC60N 2P 16 A D-curve breaker
The
A9F45216
is an Acti9 iC60N miniature circuit breaker from Schneider Electric: 2P, rated 16 A, thermal-magnetic trip unit and D tripping curve. It has two protected poles, which suits a single-phase circuit where both phase and neutral must open, or a two-wire DC circuit. our engineering team supplies the A9F45216 in Oman and the GCC as an independent supplier based in Muscat.
The reading of the reference follows the product title and datasheet fields, not a published ordering key: this unit belongs to the iC60N range with 2 poles, a 16 A rating and curve code D. The datasheet was generated on 8 Nov 2026, and the figures below follow it.
Breaking capacity and DC use of the A9F45216
Breaking capacity is the largest fault current the device can interrupt. Icu is the ultimate capacity; Ics is the service capacity after which the breaker is still expected to remain usable, shown here as a percentage of Icu. The iC60N is the standard-capacity tier of the range, with 20 kA at 220–240 V AC and 36 kA at the lowest AC band on this reference. That is enough for many final and sub-distribution circuits, but the available fault level at the board should be checked and not assumed.
Voltage
Icu
Ics
12–133 V AC
36 kA
27 kA (75 %)
220–240 V AC
20 kA
15 kA (75 %)
380–415 V AC
10 kA
7.5 kA (75 %)
440 V AC
6 kA
4.5 kA (75 %)
≤ 125 V DC
10 kA
10 kA (100 %)
Under EN/IEC 60898-1 the datasheet also lists 6000 A Icn at 400 V AC. The network type is AC/DC, and the DC ratings are limited to the voltage bands in the table (≤ 125 V DC). On a DC system the pole count matters, so check how many poles must be in series for the system voltage rather than reusing an AC arrangement.
Connections, mounting and dimensions of the A9F45216
The A9F45216 clips onto a DIN rail and occupies 4 modules of 9 mm, a width of 36 mm, with a height of 85 mm and a depth of 78.5 mm. Net weight is 0.25 kg. A toggle operates it, a contact position indicator and a trip indicato

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

SLAWXX2
Request Inquiry
More Info
ZB4BD7
Request Inquiry
More Info
ZB4BP48
Request Inquiry
More Info
ZB4BV6
Request Inquiry
More Info
ZB4BW353
Request Inquiry
More Info
Schneider
Request Inquiry
More Info
↑