Schneider Electric A9F45310 Acti9 iC60N 3P 10A D MCB


  • Part Number: A9F45310
  • Category: Electrical & Power
  • Manufacturer: Schneider Electric
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-109611
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Circuit Breakers

A9F45310: Acti9 iC60N 3P 10 A D-curve breaker
The
A9F45310
is an Acti9 iC60N miniature circuit breaker from Schneider Electric: 3P, rated 10 A, thermal-magnetic trip unit and D tripping curve. It has three protected poles for three-phase feeders and motor circuits without a neutral conductor. our engineering team supplies the A9F45310 in Oman and the GCC as an independent supplier based in Muscat.
The reading of the reference follows the product title and datasheet fields, not a published ordering key: this unit belongs to the iC60N range with 3 poles, a 10 A rating and curve code D. The datasheet was generated on 8 Nov 2026, and the figures below follow it.
Trip characteristics of the A9F45310
A thermal-magnetic breaker combines two mechanisms. The thermal element follows sustained overload and responds slowly, so a brief surge does not cause a nuisance trip. The magnetic element reacts to short-circuit current almost at once. On this unit the datasheet gives the magnetic tripping limit as 12 × In ± 20 %, which for a 10 A rating works out to roughly 96 A to 144 A, centred on 120 A. Inside that band the instantaneous element is expected to operate; below it, only the thermal element acts.
Curve D is for loads with a large starting surge. At 12 × In the instantaneous element stays quiet through the magnetising inrush of transformers and the starting current of motors, solenoids and capacitor banks, at the cost of needing a higher fault current to trip it, so cable length and loop impedance must be checked with care. The limitation class is 3 under EN/IEC 60898-1, which means the breaker restricts the let-through energy of a fault well below the prospective level.
Connections, mounting and dimensions of the A9F45310
The A9F45310 clips onto a DIN rail and occupies 6 modules of 9 mm, a width of 54 mm, with a height of 85 mm and a depth of 78.5 mm. Net weight is 0.375 kg. A toggle operates it, a contact position indicator and a trip indicator show the state, and the lever can

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

SLAWXX2
Request Inquiry
More Info
ZB4BD7
Request Inquiry
More Info
ZB4BP48
Request Inquiry
More Info
ZB4BV6
Request Inquiry
More Info
ZB4BW353
Request Inquiry
More Info
Schneider
Request Inquiry
More Info
↑