Schneider Electric A9R11280 Acti9 iID 2P 80 A 30 mA RCCB


  • Part Number: A9R11280
  • Category: Electrical & Power
  • Manufacturer: Schneider Electric
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:33
  • SKU: IS-110161
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Circuit Breakers

A9R11280: Acti9 iID 2P 80 A 30 mA type AC RCCB
The
A9R11280
is a Schneider Electric Acti9 iID residual current circuit breaker (RCCB) with 2 poles, a rated current of 80 A, a sensitivity of 30 mA and an earth-leakage protection class of type AC. It clips onto a 35 mm DIN rail, is 36 mm wide (4 modules of 9 mm) and works from 230–240 V AC at 50/60 Hz. our engineering team supplies the A9R11280 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: across the A9R references in this lane the digit after A9R follows the type (1 for type AC), the next digit follows the sensitivity, then the pole count and the rating code. That gives A9R112 followed by the rating code for 80 A. This is our reading of the pattern and the product titles, not a published ordering table, so confirm the full reference before ordering.
Installation, testing and upkeep of the A9R11280
Isolate and prove dead, clip the A9R11280 onto the DIN rail, connect conductors as shown on its diagram and torque to 3.5 N.m. After energising, press the test button on the front: the device should trip at once, and the toggle then needs resetting by hand. A failing test means the device must be replaced, not reset.
Plan for a periodic operation of the test button, usually monthly in service. Record the installed rating and sensitivity on the board schedule, and when an RCCB trips for real, find the leakage before closing it again: a repeated trip points to a damaged cable, wet equipment or an earth fault rather than a faulty device.
How the A9R11280 protects: residual current without overcurrent
An RCCB compares the current going out on the live conductors with the current coming back. If the difference reaches its sensitivity, which for this unit is 30 mA, a trip mechanism opens all 2 poles. The datasheet lists voltage-independent tripping, meaning the device does not need the line voltage to operate, so it still trips on a residual current if the supply dips or a neutral is lost upstre

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

ZBE1013
Request Inquiry
More Info
ZBVG4
Request Inquiry
More Info
A9D14820
Request Inquiry
More Info
A9R14291
Request Inquiry
More Info
A9R24440
Request Inquiry
More Info
A9R71463
Request Inquiry
More Info
↑