Selec EM368-C-CU 3-Phase CT-Operated Energy Meter, 96×96 mm


  • Part Number: EM368-C-CU
  • Category: Electrical & Power
  • Manufacturer: Selec
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-106222
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Electrical & Power > Power Meters & Power Quality

A billing-style kWh meter for CT-connected three-phase feeders
The
Selec EM368-C-CU
is a 96 x 96 mm energy meter in the EM368-C range. It is built around one job: totalising active, reactive and apparent energy on a 3-phase feeder via current transformers, with an eight-digit backlit LCD whose digits are 0.36 inch high. It also reports active and reactive power and power factor.
Where a multifunction meter fills the screen with V, I and THD, the EM368 keeps the front clean for kWh. CT primary, CT secondary, PT primary and PT secondary are user programmable, the energy registers retain their value, and a password protects the energy reset. A reverse indicator warns when CT or voltage wiring is connected the wrong way round, a common commissioning mistake on retrofit panels.
Datasheet features
3-phase power (active, reactive), power factor and energy (active, reactive, apparent)
Programmable CT/PT; RS485 Modbus RTU; single pulse output
UL listed under the -CU code (c-UL-us mark on datasheet)
Technical specification
Measurement and display
Parameter
Specification
Display
8-digit LCD with backlight, digit height 0.36 in
Energy resolution
Seven steps from 0.01k up to 10M, chosen by the CT x PT product
Method
True RMS with 100 samples in each cycle
Wiring modes
Three-phase 3-wire or 4-wire, two-phase 3-wire, single-phase 2-wire
Accuracy
1% on power and power factor; Class 1 for active energy
Inputs and supply
Parameter
Specification
Voltage window
11-300 V AC to neutral, 19-519 V AC between lines; 0.8 Mohm minimum impedance; under 0.2 VA per phase
PT entry
Primary anywhere from 100 V to 500 kV; secondary 100-500 V line to line
CT entry
5 A nominal; primary from 1 or 5 A to 10 kA with a 1 A or 5 A secondary; 120 A for one second tolerated; 0.5 VA at 5 A
Line frequency
45-65 Hz
Control power
Mains from 100 V up to 240 V AC (minus 15%, plus 12%) at 50 or 60 Hz
Outputs, mechanical and environment
Parameter
Specification
Pulse contact
Limited to 24 V DC and 100 mA, with a 100

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

MFM384
Request Inquiry
More Info
MFM376-C-CE
Request Inquiry
More Info
EM4M-3P-C-100A
Request Inquiry
More Info
EM306-C-D
Request Inquiry
More Info
MV507-230V-CE
Request Inquiry
More Info
↑