Taxonomy Path: Automation & Control > Safety Switches & Guard Locking
RLY3-OSSD200
is a SICK ReLy safety relay (part no. 1085344), an evaluation unit for safety sensors with OSSDs. It is 18 mm wide, has spring-terminal front connectors and is wired hard, so no software is needed. The data sheet lists SIL 3 (IEC 61508), PL e (ISO 13849-1) and category 4 (iso 13849-1); outputs are 2 enabling current paths (safe); 2 application diagnostic outputs (not safe); 1 test pulse output (not safe).
Safety evaluation with the RLY3-OSSD200
The OSSD version is designed to evaluate safety sensors that already have solid-state OSSD outputs, such as safety light curtains and safety laser scanners. The relay checks both channels for sequence (the data sheet lists sequence monitoring) and opens its enabling current paths when a protective device trips, with restart interlock and external device monitoring available.
Safety figures as printed: SIL 3 (IEC 61508), Category 4 (ISO 13849-1), PL e (ISO 13849-1), PFHD 1.0 x 10⁻⁹, mission time 20 years (ISO 13849-1), stop category 0 (IEC 60204-1). Reset: automatic; Manual. The two enabling current paths are N/O contacts, positively guided, switching 10 V AC … 230 V AC and 10 mA … 6 A up to a total of 12 A. Response time 10 ms.
Technical specifications
Parameter
Specification
Type code
RLY3-OSSD200
Part number
1085344
EAN
4047084415197
Product family
ReLy
Applications
Evaluation unit
Compatible sensor types
Safety sensors with OSSDs
Safety integrity level
SIL 3 (IEC 61508)
Category
Category 4 (ISO 13849-1)
Performance level
PL e (ISO 13849-1)
PFHD (mean probability of a dangerous failure per hour)
1.0 x 10⁻⁹
Stop category
0 (IEC 60204-1)
Sensor monitoring
Sequence monitoring
Restart interlock
Yes
Reset
Automatic; Manual
External device monitoring (EDM)
Yes
Connection type
Front connector with spring terminals
Inputs
2 safety inputs; 1 input for reset pushbutton or external device monitoring (EDM)
Outputs
2 enabling current paths (safe); 2 application diagnostic outputs (not safe); 1 test pulse output (not safe)
D
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |