VEGA VEGATOR 141 Level Controller for 4-20 mA Sensors


  • Part Number: VEGATOR
  • Category: Automation & Control
  • Manufacturer: VEGA
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:28
  • SKU: IS-105381
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Automation & Control > Controllers & Data Acquisition

A single-channel limit alarm for any 4…20 mA level or pressure sensor
The
VEGATOR 141
is a single-channel controller for level detection with sensors that deliver an analogue 4…20 mA signal, such as capacitive electrodes, hydrostatic pressure transmitters or process pressure transmitters. VEGA names pump control (on/off) and monitoring functions such as overfill and dry-run protection as typical applications. The module is mounted on a 35 mm carrier rail, powers an active sensor itself or accepts a passive one with its own supply, and drives an operating relay as limit alarm with an optional active fail-safe relay. The signal circuit is monitored permanently for line break and short-circuit, and the signal can come from a hazardous area.
Technical specifications
Parameter
Specification
Type
VEGATOR 141, single-channel controller for 4…20 mA sensors
Series
Module unit for carrier-rail mounting, 35 x 7.5 mm rail acc. to EN 50022/60715, detachable coded terminals
Operating voltage
24…230 V AC (-15 %, +10 %), 50/60 Hz; 24…65 V DC
Max. power consumption
2 W (8 VA)
Input
1 x 4…20 mA, active (sensor powered by VEGATOR 141) or passive (selectable)
Terminal voltage, idle
18.2 V DC ± 5 %
Internal resistance
200 Ω (active input), 100 Ω (passive input) ± 1 %
Current limitation
23 mA, permanently short-circuit proof
Fault detection
Line break ≤ 3.6 mA; short-circuit ≥ 21 mA
Switching threshold
Adjustable in the range 4…20 mA
Relay output
1 operating relay + 1 optional fail-safe relay; floating SPDT contacts
Contact rating
10 mV DC min.; max. 253 V AC / 50 V DC; 3 A AC / 1 A DC; max. 500 VA, 54 W DC
Switch-on/off delay
150 ms basic (± 10 %); adjustable 2 / 6 / 8 s (± 20 %)
Ambient temperature, protection
-20…+60 °C; IP20; overvoltage category per IEC 61010-1; pollution degree 2
Pump control and dry-run protection
Because the switching threshold is adjustable anywhere between 4 and 20 mA, one VEGATOR 141 can turn a continuous transmitter into a switch: set the threshold to the lev

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

VEGAPULS
Request Inquiry
More Info
VEGAPULS
Request Inquiry
More Info
VEGAPULS
Request Inquiry
More Info
VEGAFLEX
Request Inquiry
More Info
VEGASWING
Request Inquiry
More Info
VEGASWING
Request Inquiry
More Info
↑