Taxonomy Path: Automation & Control > Controllers & Data Acquisition
FW1012-4-2-H-D: what you receive
The Yokogawa FW1012-4-2-H-D is a twelve-channel paperless recorder from the FW1000 series. Its code reads as a recipe: FW1012 for twelve channels, -4 for a CompactFlash slot including a 512 MB card, -2 for the multi-language interface with degF and daylight-saving rules, -H for 1000 VAC isolation between measuring inputs and -D for a UL/CSA power cord. The recording unit stores trend data in a 400 MB internal file area and copies it to the card, and the datasheet photo shows a compact case with a carrying handle on top. Information below is from Yokogawa GS 04L24B01-01EN (May 2026 revision).
Scan and measurement
On the twelve-channel FW1012-4-2-H-D the scan interval is 1 s, 2 s or 5 s. A/D integration may be AUTO (the recorder follows mains frequency), 50 Hz, 60 Hz or 100 ms; selecting 100 ms restricts the scan to 2 s or 5 s. The FW1012-4-2-H-D accepts DC voltage ranges of 20 mV, 60 mV, 200 mV, 1 V, 2 V, 6 V, 20 V and 50 V, a 1 to 5 V range, thermocouples R, S, B, K, E, J, T, N, W, L, U and WRe, Pt100 and JPt100 RTDs, level or contact ON/OFF inputs and, with a shunt, DC current. Burnout detection on the FW1012-4-2-H-D (detection current about 10 microamps) can be chosen upscale or downscale per channel, and scaling spans minus 30000 to 30000.
Technical data for FW1012-4-2-H-D
Channels
12
Scan interval
1 s, 2 s, 5 s
Display
5.7-inch TFT color LCD, 240 x 320 dots
Internal memory
400 MB file storage
External medium
CF card slot with 512 MB card (suffix -4)
Case
Metal plate; bezel and cover polycarbonate
Size
144 W x 189.3 H x 184 D mm
Weight
2.3 kg without options
Supply
100 to 240 VAC rated, 90 to 264 VAC allowed, 50/60 Hz
Consumption at 100 VAC
10 VA backlight off, 15 VA normal, 35 VA maximum
Consumption at 240 VAC
15 VA, 20 VA and 45 VA
Operating ambient
0 to 50 C; 20 to 80 percent RH
Operating altitude
2000 m or less; indoor use
Mounting position
Left and right horizontal
Warm-up
At least 30 minutes
Clock accuracy
50 ppm from 0 to 5
| Delivery: | UPS, FedEx and DHL Express International delivery available Same day shipping for in-stock items on location Will negotiate custom freight & clearance details |
|---|---|
| Combined Shipping Policy: | We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling. |
| Warranty: | All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions. We record a functional test video before shipping. ✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts. |
| Returns: | No-hassle return and replacement policy. |
| Quick Quotes: | Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825. |
| Payment Options: | Wire Transfer (T/T) PayPal Visa MasterCard |