Yokogawa UT32A-D Dual-Loop Digital Indicating Controller


  • Part Number: UT32A-D
  • Category: Automation & Control
  • Manufacturer: Yokogawa
  • Product Origin: Germany / EU Germany / EU
  • Issue Date: 2026-11-26 17:35:17
  • SKU: IS-103385
  • ✓Certified Refurbished & Surplus — Save 30-60% vs New Price
  • ✓Fully Tested & Calibrated — 100% Functional Test & Report Included
  • ✓3-12 Months Warranty — Guaranteed Functional Warranty
  • ✓Fast Global Express Shipping — 3-7 Days Delivery via DHL / FedEx / UPS
Inquire via WhatsApp
New Product
On Request
✓ Original Factory Packaging
✓ Ship by: 2-4 Weeks
Never Used W/O Package
On Request
✓ Open-Box Surplus Stock
✓ Protective Industrial Packaging
✓ Ship by: 3-7 Business Days
Refurbish Grade A
On Request
✓ Inspected & 100% Function Tested
✓ 90%+ Like New Appearance
✓ Certified Refurbished
✓ Ship by: 5-10 Business Days
Refurbish Grade B
On Request
✓ Used, Repaired & Function Tested
✓ Ship by: 4-10 Business Days

Taxonomy Path: Automation & Control > Controllers & Data Acquisition

Two independent PID loops in one 48 x 96 mm panel cut-out
The
Yokogawa UT32A-D
is the dual-loop version of the UT32A. It puts two independent control loops in a narrow 48 x 96 mm panel instrument, with two universal inputs, two control outputs and a 14-segment colour LCD whose PV colour changes on alarm. It suits skids and machines that run two temperature or two pressure loops side by side, such as twin heating zones, a heater and a cooler, or two extruder or dryer zones, where two single-loop controllers would otherwise take twice the panel space.
Each loop has PID or ON/OFF control, four target setpoints, four alarm setpoints and four PID parameter sets, auto-tuning in Normal or Stable mode, the Super overshoot-suppressing and Super 2 hunting-suppressing functions, and preset output functions for stop, input error and manual operation. The control period is 200 ms. A ladder sequence function is standard and LL50A parameter-setting software (sold separately) builds ladder programs on a PC.
Technical specifications
Parameter
Specification
Model
UT32A-D dual-loop type, 48 x 96 mm panel mounting
Control
Dual-loop PID or ON/OFF; control period 200 ms
Universal inputs
2 points: thermocouple, RTD, DC voltage, DC current
Control outputs
2 points: 4-20 / 0-20 mA or voltage pulse; 2 x 1a relay, 3 A at 240 V AC or 30 V DC
Alarm outputs
3 x 1a relay, 1 A at 240 V AC or 30 V DC
Contact inputs
3 points standard
Setpoints and PID
4 target setpoints, 4 alarm setpoints and 4 PID sets per loop
Communication
RS-485 up to 38.4 kbps, 2-wire or 4-wire (Type 2 code 1)
Ladder sequence
Included as standard
Protection
IP66 front panel; NEMA 4 (hose-down test only)
Supply
100-240 V AC, 15 VA; 24 V AC/DC with /DC
Operating temperature
-10 to 50 C
Depth and weight
65 mm from panel surface; 0.5 kg or less
Inputs, outputs and model code
The two universal inputs accept thermocouples, RTDs and DC voltage or current signals, with the accuracy table shown on the datasheet (for example plus or minu

Delivery: UPS, FedEx and DHL Express
International delivery available
Same day shipping for in-stock items on location
Will negotiate custom freight & clearance details
Combined Shipping Policy: We combine shipments to reduce costs for customers purchasing multiple items. After completing your selection, request a consolidated proforma invoice including shipping and handling.
Warranty: All products are covered by Global Valve Hub — Industrial Supplies & Engineering Solutions.
We record a functional test video before shipping.
✓ 3–12 Months Functional Warranty on New, Surplus & Refurbished Parts.
Returns: No-hassle return and replacement policy.
Quick Quotes: Receive Price & Availability Today! Email sales@globalvalvehub.com or WhatsApp +1 332 322 6825.
Payment Options: Wire Transfer (T/T) PayPal Visa MasterCard

Related Products

EJX130A
Request Inquiry
More Info
EJX210B
Request Inquiry
More Info
UT52A-000-10-00
Request Inquiry
More Info
SC450G-A-A
Request Inquiry
More Info
PH8ERP-05-TN-N-E
Request Inquiry
More Info
↑